Setra Systems Model 264
Differential Pressure Transducer
1.0 GENERAL INFORMATION
Every Model 264 has been tested and calibrated before shipment. Specific
performance specifications are shown on page 3 of this Guide.
Setra Systems 264 pressure transducers sense differential or gauge (static) pres-
sure and convert this pressure difference to a proportional high level analog
output for both unidirectional and bidirectional pressure ranges. Two standard
output versions are offered: A voltage output of 0 to 5 VDC or a current output
of 4 to 20 mA.
2.0 MECHANICAL INSTALLATION
2.1 Media Compatibility
Model 264 transducers are designed to be used with air or nonconducting
gases. Use with liquids or corrosive gases will damage the unit.
2.2 Environment
The operating temperature limits of the 264 are 0°F to +175°F (-18°C to +79°C).
The compensated temperature range is 0°F to +150°F (-18°C to +65°C).
2.3 Pressure Fittings
The Model 264 is designed to be used with 3/16” I.D. push-on tubing. Both the
positive (high) pressure port and the reference (low) pressure port are located
on the front of the unit, labeled “HIGH” and “LOW” respectively. For best
results (shortest response times), 3/16” I.D. tubing is suggested for tubing
lengths up to 100 feet long, 1/4” I.D. for tubing lengths up to 300 feet, and 3/8”
I.D. for tubing lengths up to 900 feet.
3.0 ELECTRICAL INSTALLATION
If the Model 264 is supplied with the optional Conduit Enclosure, access the
electrical terminations by removing the cover. The output of 0 to 5 VDC or
4 to 20 mA is designated by specific Code numbers in the configurable part
number; i.e., 2641xxxxx 11xx x, where 11 designates the 4 to 20 mA output;
2641xxxxx 2Dxx x, where 2D designates the 0 to 5 VDC output. The output is
also shown on the 264 label.
For CE Compliance, a shielded cable with both ends properly grounded is
required.
3.1 Voltage Output Units
The Model 264 voltage output is a 3-wire circuit, with three terminals
available for wiring. These terminals have the designation COM, EXC and OUT
(See Diagram 1). The power supply and signal references are commoned on
the circuit (See Diagram 2). The 264 voltage output can operate from 9-30 VDC
excitation. The 264 has a 0 - 5 VDC output.
Installation Guide
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Installation Guide

Setra Systems Model 264Differential Pressure Transducer 1.0 GENERAL INFORMATION Every Model 264 has been tested and calibrated before shipment. Spe

Page 2 - 4.0. CALIBRATION

2 4.0. CALIBRATION The 264 transducer is factory calibrated and should require no field adjust- ment. Generally, the mounting position will have a

Page 3 - Accuracy RSS

3 location of zero adjustment.) For 0-5 VDC output units, the factory settings are 0.050VDC (±50mV) for unidirectional pressure ranges and 2.5 V

Page 4

4 159 Swanson Road, Boxborough, MA 01719-1304 Tel: 800-257-3872/978-263-1400 SS0471 Rev.G 08/14/096.0 RETURNING PRODUCTS FOR REPAIRPlease contact